ASHRAE CLIMATIC DESIGN CONDITIONS 2009/2013/2017
dimok911@gmail.com
Contacts
CLIMATIC DESIGN CONDITIONS 2009 SI
Annual Design Conditions
Annual Heating and Humidification Design Conditions.
Annual Cooling, Dehumidification, and Enthalpy Design Conditions.
Extreme Annual Design Conditions.
Monthly Design Conditions
Temperatures, Degree-Days, and Degree-Hours.
Monthly Design Dry-Bulb, Wet-Bulb, and Mean Coincident Temperatures.
Mean Daily Temperature Range.
Clear-Sky Solar Irradiance.
The top part of the table contains station information as follows:
- Name of the observing station, state (USA) or province (Canada), country.
- Latitude of station, °N/S.
- Longitude of station, °E/W.
- Elevation of station, m.
- Standard pressure at elevation, in kPa.
- Time zone, h ± UTC.
- Period analyzed (e.g., 82-06 = data from 1982 to 2006 were used).
Annual Design Conditions
Annual climatic design conditions are contained in the first three sections following the top part of the table. They contain information as follows:
Annual Heating and Humidification Design Conditions.
- Coldest month (i.e., month with lowest average dry-bulb temperature; 1 = January, 12 = December).
- Dry-bulb temperature corresponding to 99.6 and 99.0% annual cumulative frequency of occurrence (cold conditions), °C.
- Dew-point temperature corresponding to 99.6 and 99.0% annual cumulative frequency of occurrence, °C; corresponding humidity ratio, calculated at standard atmospheric pressure at elevation of station, grams of moisture per kg of dry air; mean coincident drybulb temperature, °C.
- Wind speed corresponding to 0.4 and 1.0% cumulative frequency of occurrence for coldest month, m/s; mean coincident dry-bulb temperature, °C.
- Mean wind speed coincident with 99.6% dry-bulb temperature, m/s; corresponding most frequent wind direction, degrees from north (east = 90°).
Annual Cooling, Dehumidification, and Enthalpy Design Conditions.
- Hottest month (i.e., month with highest average dry-bulb temperature; 1 = January, 12 = December).
- Daily temperature range for hottest month, °C [defined as mean of the difference between daily maximum and daily minimum drybulb temperatures for hottest month].
- Dry-bulb temperature corresponding to 0.4, 1.0, and 2.0% annual cumulative frequency of occurrence (warm conditions), В°C; mean coincident wet-bulb temperature, °C.
- Wet-bulb temperature corresponding to 0.4, 1.0, and 2.0% annual cumulative frequency of occurrence, °C; mean coincident drybulb temperature, °C.
- Mean wind speed coincident with 0.4% dry-bulb temperature, m/s; corresponding most frequent wind direction, degrees true from north (east = 90°).
- Dew-point temperature corresponding to 0.4, 1.0, and 2.0% annual cumulative frequency of occurrence, °C; corresponding humidity ratio, calculated at the standard atmospheric pressure at elevation of station, grams of moisture per kg of dry air; mean coincident dry-bulb temperature, °C.
- Enthalpy corresponding to 0.4, 1.0, and 2.0% annual cumulative frequency of occurrence, kJ/kg; mean coincident dry-bulb temperature, °C.
- Number of hours between 8 AM and 4 PM (inclusive) with dry-bulb temperature between 12.8 and 20.6°C.
Extreme Annual Design Conditions.
- Wind speed corresponding to 1.0, 2.5, and 5.0% annual cumulative frequency of occurrence, m/s.
- Extreme maximum wet-bulb temperature, °C.
- Mean and standard deviation of extreme annual minimum and maximum dry-bulb temperature, °C.
- 5-, 10-, 20-, and 50-year return period values for minimum and maximum extreme dry-bulb temperature, °C.
Monthly Design Conditions
Monthly design conditions are divided into subsections as follows:
Temperatures, Degree-Days, and Degree-Hours.
- Average temperature, °C. This parameter is a prime indicator of climate and is also useful to calculate heating and cooling degreedays to any base.
- Standard deviation of average daily temperature, °C. This parameter is useful to calculate heating and cooling degree-days to any base. Its use is explained in the section on Estimation of Degree-Days.
- Heating and cooling degree-days (bases 10 and 18.3°C). These parameters are useful in energy estimating methods. They are also used to classify locations into climate zones in ASHRAE Standard 169.
- Cooling degree-hours (bases 23.3 and 26.7°C). These are used in various standards, such as Standard 90.2-2004.
Monthly Design Dry-Bulb, Wet-Bulb, and Mean Coincident Temperatures.
These values are derived from the same analysis that results in the annual design conditions. The monthly summaries are useful when seasonal variations in solar geometry and intensity, building or facility occupancy, or building use patterns require consideration. In particular, these values can be used when determining air-conditioning loads during periods of maximum solar radiation. The values listed in the tables include
- Dry-bulb temperature corresponding to 0.4, 2.0, 5.0, and 10.0% cumulative frequency of occurrence for indicated month, °C; mean coincident wet-bulb temperature, °C.
- Wet-bulb temperature corresponding to 0.4, 2.0, 5.0, and 10.0% cumulative frequency of occurrence for indicated month, °C; mean coincident dry-bulb temperature, °C.
For a 30-day month, the 0.4, 2.0, 5.0 and 10.0% values of occurrence represent the value that occurs or is exceeded for a total of 3, 14, 36, or 72 h, respectively, per month on average over the period of record. Monthly percentile values of dry- or wet-bulb temperature may be higher or lower than the annual design conditions corresponding to the same nominal percentile, depending on the month and the seasonal distribution of the parameter at that location. Generally, for the hottest or most humid months of the year, the monthly percentile value exceeds the design condition for the same element corresponding to the same nominal percentile.
A general, very approximate rule of thumb is that the n% annual cooling design condition is roughly equivalent to the 5n% monthly cooling condition for the hottest month; that is, the 0.4% annual design dry-bulb temperature is roughly equivalent to the 2% monthly design dry-bulb temperature for the hottest month; the 1% annual value is roughly equivalent to the 5% monthly value for the hottest month, and the 2% annual value is roughly equivalent to the 10% monthly value for the hottest month.
Mean Daily Temperature Range.
These values are useful in calculating daily dry- and wet-bulb temperature profiles. Three kinds of profile are defined:
- Mean daily temperature range for month indicated, В°C (defined as mean of difference between daily maximum and minimum drybulb temperatures).
- Mean daily dry- and wet-bulb temperature ranges coincident with the 5% monthly design dry-bulb temperature. This is the difference between daily maximum and minimum dry- or wet-bulb temperatures, respectively, averaged over all days where the maximum daily dry-bulb temperature exceeds the 5% monthly design dry-bulb temperature.
- Mean daily dry- and wet-bulb temperature ranges coincident with the 5% monthly design wet-bulb temperature. This is the difference between daily maximum and minimum dry- or wet-bulb temperatures, respectively, averaged over all days where the maximum daily wet-bulb temperature exceeds the 5% monthly design wet-bulb temperature.
Clear-Sky Solar Irradiance.
Clear-sky irradiance parameters are useful in calculating solar-related air conditioning loads for any time of any day of the year. Parameters are provided for the 21st day of each month. The 21st of the month is usually a convenient day for solar calculations because June 21 and December 21 represent the solstices (longest and shortest days) and March 21 and September 21 are close to the equinox (days and nights have the same length). Parameters listed in the tables are
- Clear-sky optical depths for beam and diffuse irradiances, which are used to calculate beam and diffuse irradiance.
- Clear-sky beam normal and diffuse horizontal irradiances at solar noon. These two values can be calculated from the clear-sky optical depths but are listed here for convenience.
Temperature is the measure of the intensity or level of heat.
Dry Bulb Temperature (DB, db, DBT, dbt) is the temperature registered by an ordinary thermometer. db
represents the measure of sensible heat, or the intensity of heat.
Wet Bulb Temperature (WB, wb, WBT, wbt) is the temperature registered by a thermometer whose bulb is
covered by a wetted wick and exposed to a current of a rapidly moving air having a velocity of around 5 m/s.
WB is measured by a sling psychrometer which has a set of dry and wet bulb thermometers. The psychrometer
is whirled at such revolutions per second that the velocity of the bulb will be 5 m/s approx (in still air).
Relative Humidity (RH, rh); (expressed in percentage) is the ratio of actual partial pressure of water vapour
to its saturation pressure corresponding to the same db. Alternate definitions are – ratio of amount of moisture
present in the air to the amount the same air holds at saturation at the same temperature, It indicates the ability
of air to absorb additional moisture.
Dew Point (DP, DPT) is the temperature at which water vapour in moist air starts condensing when it is cooled.
Humidity Ratio is the weight of water contained in the air per unit of dry air. This is often expressed as kgs
of moisture per kg of dry air or grams of moisture per kg of dry air (g/kg).
Specific Volume is the cubic meter of moist air per kg of dry air represented as m3/kg.
Enthalpy is the heat energy content of moist air. It is expressed in kJ/kg and represents the heat energy due to
temperature and moisture in the air. Lines of constant enthalpy (OH in Figure A) run diagonally downward from
left to right across the chart. Lines of constant enthalpy and constant wet-bulb temperature lie close to each other.
Accordingly, they coincide in many elementary charts, but with both values being indicated on the common line.